Volt Drop

The voltage drop in a cable is directly proportional to the circuit current and the length of the cable run.  BS7671:2011 limits the voltage drop permitted between the origin of the installation and the terminals of the load to 3% of the nominal supply voltage for lighting circuits and 5% of the nominal supply voltage for other circuits.

To calculate the volt drop of a circuit, you need to know the tabulated value of voltage drop (mV/A/m) listed in appendix 4 of BS7671, the design current (Ib) and the length of the circuit.

voltage drop = \frac{(mV/A/m) \times I_{b} \times L}{1000}

For example, a 4.5kW 230V 50Hz single phase motor with a power factor of 0.7 and an efficiency of 75% is wired with pvc insulated single core cables in steel conduit.  The length of the run is 30m, the ambient temperature is 35degC and the circuit will be protected by BS88 fuses.  Calculate the size of the conductors if the voltage drop in the circuit must not exceed 5V.

Firstly we will calculate the design current (Ib),

P=\frac{Output}{Efficiency}

P=\frac{4500}{0.75}

P=6000 W

I_{b} = \frac{P}{U \times \textit{p.f.}}

I_{b} = \frac{6000}{230 \times 0.7}

= 37.3 A

Minimum BS88 fuse rating (In) will be 40A, Correction factor for ambient temperature (Ca) for 35degC will be 0.94 and the correction factor for fuses (Cr) is 1 for BS88 fuses.

Thus the minimum tabulated current rating (It) is calculated

I_{t} = \frac{40}{0.94 \times 1}

= 42.55 A

Selecting a 10mm cable from BS7671 Table 4D1A which can carry 57A and has a 4.4 mV/A/m tabulated volt drop listed in Table 4D1B, we can calculate the volt drop as follows.

voltage drop = \frac{4.4 \times 37.3 \times 30}{1000}

=4.91V

Therefore the 10mm cable will be suitable.

What our clients say...

  • We asked Connectus Electrical to carry out the design and install for the new electrical supplies to our equipment for our new robotic cell manufacturing unit.  We were on a very tight schedule and with the help Connectus Electrical’s team, the project was operational on time.

    Ewan McConnell
    ,
    Managing Director, Magor Designs
  • We have had a long standing relationship with Connectus Electrical Ltd based on excellent service and competitive pricing. Following a weekend flood that damaged our offices, reception, and meeting rooms we called out Connectus who had temporary power set up ready for Monday morning that minimised any business disruption. Connectus subsequently carried out all electrical repairs, rewiring, and data services; we were delighted with the standard of works and the way in which their team carried them out.

    Richard Green
    ,
    Operations Director, Bearmach Ltd
  • One of our customers in Cardiff wanted me to pass on her thanks to one of your engineers. She said that she was very impressed with the level of service she received. He sorted out the problem efficiently and took the time to explain everything to her. She described him as a ‘marvelous bloke.

    Georgina Lewis
    ,
    Westward Energy Services Ltd
  • One of our in house maintenance engineers was off sick for six weeks.  Connectus Electrical were able to supply a maintenance electrician for the duration at short notice.  We were very impressed with their service engineer.

    Lee Murphy
    ,
    Senior Team Leader, Macmillan Distribution Ltd